Lenze 8200 Frequency inverters Uživatelský manuál Strana 144

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 311
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 143
Configuration
8200SHB0199
7-7
Acceptance acknowledged with SH + PRG when the controller is
inhibited.
(Labelled with [Cxxx]” in the code table.)
The controller only accepts the changed parameter when the controller is inhibited
and after pressing SH + PRG.
1. In the operating level you inhibit the controller by pressing STP.
2. Change from the operating level to the code level by pressing PRG.
3. Select a code with or .
4. Change to parameter set PAR1 by pressing SH.
- If necessary, press SH again to change to parameter set PAR 2.
5. If PAR1 or PAR2 is blinking, change the parameter with or .
6. Press SH + PRG.
- STO is displayed for approx. 1 s.
- The program jumps back to the code level.
7. Change to the operating level by pressing PRG.
- The changed parameter is now stored permanently.
8. Enable the controller again using RUN.
- The controller now works with the new parameter.
Note!
Fast loading of the factory setting for 820X:
Press the keys and at the same time in the parameter level to load the factory
setting of the selected code.
Show/Hide Bookmarks
Zobrazit stránku 143
1 2 ... 139 140 141 142 143 144 145 146 147 148 149 ... 310 311

Komentáře k této Příručce

Žádné komentáře