Function library
Positioning control
3.4.11 Program operation
3−71
l
EDSVS9332P−EXT DE 2.0
Tip!
l The program processing is continued to the "Program end" even if the start signal is reset
immediately.
l If the start signal is still applied at "program end" the program will be restarted automatically
every time.
l A new edge at POS−PRG−START is required after interrupting the program processing (e.g. by
controller inhibit) or by a fault message.
Afterwards the program is continued from the same position (status display: C1283=15).
The start signal will only be accepted in program operation and when the controller is enabled.
The controller is enabled if
1. the power stage is supplied (DCTRL−RDY=1),
2. no fault applies (DCTRL−TRIP=0, DCTRL−FAIL−QSP=0),
3. the control enable signal is applied (DCTRL−CINH=0)
4. quick stop (QSP) is not activated (MCTRL−QSP−OUT=0)
5. manual operation is not activated (POS−MANUAL=0, C1280.B4=0)
6. program reset is not activated (POS−PRG−RESET=0, C1280.B2=0)
Stopping the program (PRG_STOP)
l POS−PRG−STOP = HIGH or C1280.B1 = 1 (Program stop" in the GDC dialog "Control").
The signal "program stop" interrupts the program processing and the running positioning
process. The drive is stopped with the current delay of the program set (no influence of
POS−A−OVERRID).
l POS−PRG−STOP = LOW and C1280.B1 = 0 (Program stop" in the GDC dialog "Control").
The program is continued from the same position when Program stop"=LOW. The
positioning process is finished with the current profile parameters of the PS.