Industrial PC | Parameter setting & configuration
Parameter reference
Industrial PC extension modules
200 L 2.5 EN - 01/2012
C1596/12
C1596/13
C1596/14
C1596/15
C1596/16
Parameter | Name:
C1596/12 | ECAT: DC support
Data type: UNSIGNED_8
Index: 22979.12
d
=
0x59C3.0x0C
h
Support of the distributed clocks by the slave:
Value "0": Distributed clocks are not supported.
Value "1": Distributed clocks are supported.
Display range (min. value | unit | max. value)
0 1
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1596/13 | ECAT: DC support - 64 bits
Data type: UNSIGNED_8
Index: 22979.13
d
=
0x59C3.0x0D
h
Support of the distributed clocks (64 bits) by the slave:
Value "0": Distributed clocks (64 bits) are not supported.
Value "1": Distributed clocks (64 bits) are supported.
Display range (min. value | unit | max. value)
0 1
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1596/14 | Mailbox support
Data type: UNSIGNED_8
Index: 22979.14
d
=
0x59C3.0x0E
h
Mailbox support by the slave:
Value "0": Mailbox is not supported.
Value "1": Mailbox is supported.
Display range (min. value | unit | max. value)
0 1
; Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C1596/15 | ECAT: Requested state
Data type: UNSIGNED_32
Index: 22979.15
d
=
0x59C3.0x0F
h
This code displays the state specified by the master. At the same time, the user can request a state here.
Note: This is a debug code. Setting this parameter only sets the state of the currently selected slave. All other nodes
remain in their present states. Changing the state of the slave via this code may cause unstable system states.
Selection list (Lenze setting printed in bold)
0 Invalid
1Init
2 Pre-Operational
4 Safe Operational
8Operational
; Read access ; Write access CINH PLC STOP ; No transfer
Parameter | Name:
C1596/16 | ECAT: Current state
Data type: UNSIGNED_32
Index: 22979.16
d
=
0x59C3.0x10
h
Display of the current state of the slave