
Electrical installation
Power terminals
Mains connection
4
87
EDKCSCE040 DE/EN/FR 3.0
Fuses
Use the following circuit−breakers or UL−approved fuses to protect the mains
cable (see Fig. 4−2 ( 86)):
Power supply
module
Dimensioning according to IEC/EN Dimensioning to UL
Circuit−breaker Cable
cross−section
[mm
2
]
UL fuse AWG
ECSxE012 C16 A 2.5 25A 12
ECSxE020 C16 A 2.5 25A 12
ECSxE040
: C 40 A 10
1)
35 A 8
1)
/: , C 32 A 6 35 A 10
: C 40 A 6
2)
35 A 10
2)
: C 40 A 10 35 A 8
1) Cable without wire end ferrule or with pin−end connector
2) Cable length max. 30 cm
Warnings!
ƒ Use UL−approved cables, fuses and fuse holders only.
ƒ UL fuse:
– Voltage 500 ... 600 V
– Tripping characteristic "H", "K5" or "CC"
Replacing defective fuses
Danger!
Hazardous electrical voltage
Components can carry hazardous voltages up to 3 minutes after
power−off.
Possible consequences:
ƒ Death or severe injuries when touching the device.
Protective measures:
ƒ Replace fuses in the deenergised state only.
– Set controller inhibit (CINH) for all axis modules in DC−bus
operation and disconnect all power supply modules from the
mains.
Komentáře k této Příručce