Function library LenzeDrive.lib
Appendix
3−2
L
LenzeDrive.lib EN 1.7
Code InfoIMPORTANTPossible settingsLCDCode InfoIMPORTANT
ChoiceLenze
LCD
C0190 byArithFunction 0 0 OUT = C46
1 C46 + C49
2 C46 − C49
3 C46 * C49
4 C46 / C49
5 C46/(100 − C49)
Arithmetic block in the function block
L_NSET1
Combines main setpoint C0046 and
additional setpoint C0049.
^ 2−73
C0220 dnTirAdd 0.000 0.000 {0.001 sec} 999.900 Acceleration time T
ir
of the additional
setpoint for L_NSET1
Related to the speed change
0 ... n
max
.
^ 2−73
C0221 dnTifAdd 0.000 0.000 {0.001 sec} 999.900 Deceleration time T
if
of the additional
setpoint for L_NSET1
Related to the speed change
n
max
... 0.
^ 2−73
C0222 nVp 1.0 0.1 {0.1} 500.0 Gain V
p
of L_PCTRL1 ^ 2−79
C0223 nTn 400 20 {1 msec} 99999
99999 ms switched off
Integral component T
r
of L_PCTRL1 ^ 2−79
C0224 nKd 0.0 0.0 {0.1} 5.0 Differential component K
d
of L_PCTRL1 ^ 2−79
C0241 nIEqOHysteresis 1.00 0.00 {0.01 %} 100.00
100 % = n
max
Threshold ramp generator for main
setpoint of L_NSET1
Input = output
^ 2−73
C0260 nHighLimit 100.00 −199.99 {0.01 %} 199.99 Upper limit of L_MPOT1
Mandatory is: C0260 > C0261
^ 2−70
C0261 nLowLimit −100.0 −199.99 {0.01 %} 199.99 Lower limit of L_MPOT1
Mandatory is: C0261 < C0260
^ 2−70
C0262 wTir 10.0 0.1 {0.1 s} 6000.0 Acceleration time T
ir
of L_MPOT1
Related to change 0 ... 100 %.
^ 2−70
C0263 wTif 10.0 0.1 {0.1 s} 6000.0 Deceleration time T
if
of L_MPOT1
Related to change 0 ... 100 %.
^ 2−70
C0264 byFunction 0
Deactivation function of L_MPOT1
Function which is executed when
motor pot is deactivated via the
input MPOT1−INACTIVE.
^ 2−70
0 No function
1 Down to 0 %
2 Down to C261
3 Jump 0 %
4 Jump to C261
5 Up to C260
No change
Deceleration with T
if
to 0 %
Deceleration with T
if
to C0261
Inhibit with T
if
= 0 to 0 %
Inhibit with T
if
= 0 to C0261
Acceleration with T
ir
to C0260
^ 2−70
C0265 byInitFunction 0
Initialisation function of L_MPOT1
Value which is accepted during
mains switching and activated
motor pot.
^ 2−70
0 Power off
1 C0261
2 0 %
Value during mains failure
Lower limit of C0261: 0 %
^ 2−70
C0325 nVp2Vdapt 1.0 0.1 {0.1} 500.0 Gain adaptation (V
p2
) of L_PCTRL1 ^ 2−79
C0326 nVp3Adapt 1.0 0.1 {0.1} 500.0 Gain adaptation (V
p3
) of L_PCTRL1 ^ 2−79
C0327 nSet2Adapt 100.00 0.00 {0.01 %} 100.00 Adaptation n
set2
of L_PCTRL1
Set speed threshold of the process
controller adaptation
Mandatory is: C0327 > C0328
^ 2−79
C0328 nSet1Adapt 0.00 0.00 {0.01 %} 100.00 Adaptation n
set1
of L_PCTRL1
Set speed threshold of the process
controller adaptation
Mandatory is: C0328 < C0327
^ 2−79
Komentáře k této Příručce