Function library LenzeIOSystem.lib
Function blocks
4.8 L_IOParPDO15 − Parameterisation function
4−19
L
LenzeIOSystem.lib EN 1.7
Note!
Features and use of the L_IOParPDO15 FB.
· Use the L_IOParPDO15 FB last in a sequencer consisting of several FBs for parameterisation.
By means of the L_IOParPDO15 FB, parameterisation of the I/O system is carried out.
· For sending the NMT telegram, the controller has to be in the Operational CAN status,
therefore parameterise the controller as master. After the boot−up time has expired, the state
change from Pre−operational to Operational is automatically effected.
· If several IO systems (stations) are parameterised with standard values via the
L_IOParPDO15 FB on the system bus, an identifier collision between the individual PDOs of
these stations can occur. Therefore check the identifiers used.
After changing to the Operational CAN status, the current process image of the I/O system is sent.
ð Inputs (Variable type: VAR_INPUT)
Variable name Data type Information/possible settings
bExecute BOOL
Execute write request
FALSE ä TRUE Write request is executed
byNodeAdr Byte Device address: 1 − 63
bInitIOSystem BOOL
Initialise I/O system after parameterisation
TRUE · Value acceptance by reset node
· I/O system is re−initialised, state change to Operational
FALSE · No value acceptance
· I/O system is not initialised
wCobID_RxPDO1
...
wCobID_RxPDO5
WORD
Setting identifiers
Default values: input wiring = 0
RxPDO = receive identifiers from the I/O system
Identifiers can be optionally set by value selection.
If the input wiring is "0", the identifiers are composed as follows.
Note!
The basic identifiers are not settled in the pre−assigned area of the standard system
bus.
ID range: 384−831
By this, crossovers of the ID with the free CAN objects which the IO−lib is based on
are avoided.
RxPDOX Identifier = Basic ID + Node address
RxPDO1 837 835 2
RxPDO2 840
RxPDO3 845
RxPDO4 850
RxPDO5 855
byTransmissionType_RxPDO1
...
byTransmissionType_RxPDO5
Byte
Transmission mode
0 Event−controlled
1 Time−controlled
2 Event−controlled with superimposed cycle time
tCycleTime_RxPDO1
...
tCycleTime_RxPDO5
Time Cycle time: t = 0 − 65535 ms