Commissioning
Possible settings via the front DIP switches
5
EDKMF2113 DE/EN/FR 5.1
61
H1inbet−Merker_hidden statusanzeige
Possible settings via the front DIP switches
Note!
If switches S1 ... S8 remain in the Lenze setting OFF, the configurations set
under the codes C1910, C1911 and C1912 will become active when the device
is switched on.
If one or several switches of switches S1 ... S7 are switched over to ON,
ƒ all switch positions are valid!
ƒ the following must be set:
Number of process data words (PCD),
Number of parameter data words (PCP), and
Device control AIF−CTRL / DRIVECOM control
Switch off the voltage supply of the communication module and afterwards on again to
activate changed settings.
As a maximum, the data word sum (PCD + PCP) is to amount to 10 words.
Please note that only the switch combinations listed in the following tables represent
defined states. If the settings are unacceptable, the yellow LED at the front of the
communication module will start blinking with f = 8Hz.