Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17 85
11 Diagnostics
11.1 LED status displays
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.1.1 Module status displays
The LEDs MS, ME and DE show the module status.
[11-1] LEDs MS, ME, DE
E84YCET006
ME
DE
MS
LED Colour State Description
MS green on
The communication module is supplied with voltage and is
connected to the standard device.
blinking
The communication module is supplied with voltage, but has no
connection to the standard device (the standard device is switched
off, in the initialisation phase, or not available).
ME red on
An error has occurred in the communication module.
DE red on
The communication module is not accepted by the standard device,
or the standard device is not active. (See notes in the documentation
for the standard device).
200 ms
200 ms