Lenze EVS9332xP Uživatelský manuál Strana 255

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 445
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 254
Configuration
Monitoring
Controller current load (I x t monitoring)
8
8.2
8.2.6
8.2−5
EDSVS9332P EN 5.0−07/2013
8.2.6 Controller current load (I x t monitoring)
200 %
I
r
150 %
100 %
70 %
10 60 120 180
t [s]
9300std228
Fig. 8.2−3 I × t diagram
I
r
Device output current
100 % continuous thermal current at C0022 £ 1.5 I
r
70 % continuous thermal current at C0022 > 1.5 I
r
The I × t monitoring monitors the current load of the controller. The current
load is calculated from the mean value of the motor current over the
acquisition period of 180 s.
The monitoring is set in such a way that the following operation modes are
possible:
ƒ Continuously with device output current = I
r
.
ƒ £ 60 s with device output current £ 1.5 x I
r
.
A fault initiates TRIP OC5. Other responses cannot be set.
Zobrazit stránku 254
1 2 ... 250 251 252 253 254 255 256 257 258 259 260 ... 444 445

Komentáře k této Příručce

Žádné komentáře