System bus (CAN) for Lenze PLC devices
Configuration (AIF interface)
4−3
l
PLC−Systembus EN 2.0
4.3 Node address (node ID)
Assign a node address − also called Node ID − within the range of 1 to 63 to each node within the
system bus network as a definite identification.
· The same node address may not be allocated more than once within the network.
· The configuration of the node address for the AIF interface of the PLC is effected via code
C2350:
Code LCD
Possible settings
Information
Lenze Selection
C2350 XCAN address 1 1 {1} 63 System bus − node address
· Save changes with C0003 = 1.
· Changes are only valid after
reset node!
Allocation of the node address for the data exchange among Lenze devices
If Lenze devices are provided with node addresses in a consistent ascending order, the identifiers
of the event−controlled data objects (XCAN2_IO/XCAN3_IO) are set in way by the factory which
enables a communication from one device to the other:
L
Node-ID 1
XCAN2_OUT
XCAN2_IN
XCAN3_OUT
XCAN3_IN
L
Node-ID 2
XCAN2_OUT
XCAN2_IN
XCAN3_OUT
XCAN3_IN
L
Node-ID 3
Fig. 4−1 Data exchange among Lenze devices