Lenze DSD Uživatelský manuál Strana 350

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 496
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 349
11 Drive Dimensioning
11.6 Inverters
350
Lenze · Drive Solution Designer · Manual · DMS 4.2 EN · 12/2013 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.6.1.4 Overcurrent operation for i700
Temporarily, the power supply modules and axis modules can be operated with output currents
higher than the rated current.
Two utilisation cycles are specified, each with a running time and a recovery time. A running time
must be followed by a recovery time. The current must not exceed the indicated value in the recov-
ery time. All values refer to the rated output current.
15-s cycle: pulse utilisation
3 s running time with peak current (200 %)
12 s recovery time with limited current (66 %)
180-s cycle: permanent utilisation
60 s running time with peak current (150 %)
120 s recovery time with limited current (75 %)
The illustration below shows typical curves of utilisation cycles:
[11-21] Overcurrent capability i700 at 40 °C
15-s cycle: pulse utilisation Equation:
Peak current
Limited current during the recovery time
t
1
Running time with peak current
t
2
Recovery time with limited current
180-s cycle: permanent utilisation Equation:
Peak current
Limited current during the recovery time
t
3
Running time with peak current
t
4
Recovery time with limited current
t
0
100 %
1
0
2
I [%]
N,out
t
2
t
3
t
4
t
1
At
1
Ct
2
+
t
1
t
2
+
--------------------------------
100 %
At
3
C4+
t
3
t
4
+
------------------------------
100 %
Zobrazit stránku 349
1 2 ... 345 346 347 348 349 350 351 352 353 354 355 ... 495 496

Komentáře k této Příručce

Žádné komentáře