Codes
Communication−relevant Lenze codes
14
l
132
EDSMF2178IB EN 3.0
C1859/C2359:
Display of DIP switch position
Code Subcode Index
Possible settings
Data type
Lenze Selection
C1859 22716 =
0x58BC
g
U16
C2359 22216
d
=
0x56C8
U32
The DIP switch position is indicated as a hexadecimal number with the initialisation of the
communication module.
) Note!
In case of 9300 Servo PLC, Drive PLC and ECS, the value will be transferred to
the standard device when the communication module is initialised.
DIP switch valencies for hexadecimal calculation
Switch 1 2 3 4 5 6 7 8 9 10
Value 512 256 128 64 32 16 8 4 2 1
Bit 15 ... 10 9 8 7 6 5 4 3 2 1 0
Example for DIP switch position
ƒ Switches 3, 5, 6, 7 = ON (address 23)
ƒ Switches 8, 9, 10 = OFF (baud rate 500 kbit/s)
The sum of the corresponding valencies "0xB8" (184) is displayed when code
C1859/C2359 is read.