L-force | PLC Designer
Lenze Specific Functions
32 DMS 4.1 EN 03/2011 TD29
Function block L_SMC_AbortTrigger (for EtherCAT)
Function library: L_SM3_DriveUtil.lib
Note: This block only supports EtherCAT axes at the present time.
Inputs (VAR_IN)
Designator / Data type Info / Setting options
Execute / BOOL When a new positive edge is set, all outputs of the block are reset to the
initial values.
TriggerInput /
L_SMC_Trigger_REF
Structure for configuration of the measurement
Axis / AXIS_REF Selection of the drive
Outputs (VAR_OUT)
Designator / Data type Value / Meaning
Done / BOOL Function block L_SMC_TouchProbe has been aborted.
Error / BOOL Error detection: An error has occurred in task assignment.
ErrorID / INT Error number
Error messages
The following error messages have been stored:
Error number [hex] Description
0x0001 Error in assignment of task to the block:
Input data do not match activated TP task assignment on this channel. If no
task is active on the TP channel, an error message is not generated.
TouchProbeSelect > 1 in the case of ECSxM
TouchProbeSelect > 2 in the case of 9400