Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17 125
9 Function library L_IODrvEtherCAT.lib
9.2 CoE Interface
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.2 L_ETC_CoE_SdoRead (FB)
This function block triggers uploading of a CoE object (SDO) from the slave or from the master.
Visualisation: VISU_L_ETC_CoE_SdoRead
Inputs (VAR_INPUT)
Note!
For executing the function block, the EtherCAT master and the slave must be at least in
the "Pre-Operational" state.
L_ETC_CoE_SdoRead
BOOL xExecute xDone BOOL
BOOL xAbort xBusy BOOL
USINT usiCom xError BOOL
UINT uiDevice eErrorCode L_ETC_ERRORCODE
WORD wIndex udiSdoAbort UDINT
BYTE bySubindex szDataRead CAA_SIZE
UDINT udiTimeOut
CAA_PVOID pBuffer
CAA_SIZE szSize
Identifier/data type Meaning/possible settings
xExecute
BOOL
A positive edge (TRUE) triggers a read request (uploading) of a CoE object.
xAbort
BOOL
A positive edge (TRUE) aborts a running read request (upload).
xAbort is currently not supported in the Lenze control technology R3.x.
usiCom
USINT
EtherCAT master instance number
In the Lenze control technology R3.x, only instance number 1 is currently
supported. usiCom has been pre-assigned with 1, so that the input can be left
open.
A value that does not equal 1 causes the error ETC_E_INVALIDPARM
(0x9811000B).
uiDevice
UINT
EtherCAT address (station address) of the master/slave
The station addresses are assigned by the master during the start-up phase
(fixed-address assignment, see also Addressing of the slaves
( 22)).
The address ’0’ directly accesses the object directory of the EtherCAT master.
The first EtherCAT slave is given the address ’1001’, the second the address ’1002’
and so on.
The EtherCAT addresses cannot be altered.
wIndex
WORD
CANopen index to be read in the object directory of the master or slave.
Formula for converting a Lenze code number into a CANopen index: Index =
0x5FFF - code number
bySubindex
BYTE
Subindex in the object directory of the master or slave.
udiTimeout
UDINT
Timeout in milliseconds (ms)
The value 0 is not permissible and causes the error ETC_E_INVALIDPARM
(0x9811000B).