9300 Servo PLC
Appendix
3−112
L
9300 Servo PLC EN 5.1
Fault message RemedyCauseDescription
No.
RemedyCauseDescription
Display
x058 OH8 Motor temperature via inputs T1 and T2 is
too high.
Motor is thermally overloaded due to:
Impermissible continuous current
Frequent or too long acceleration
processes
Check drive dimensioning.
Switch off monitoring (C0585 = 3).
Terminals T1 and T2 are not connected Connect PTC/temperature contact.
x061 CE0 Automation interface (AIF) communication
error
Faulty transfer of control commands via AIF. Plug in the communication
module/keypad XT firmly, screw down, if
necessary.
Switch off monitoring (C0126 = 3).
x062 CE1 Communication error on the process data
input object CAN1_IN
CAN1_IN object receives faulty data or
communication is interrupted.
Check wiring at X4.
Check sender.
Increase monitoring time under
C0357/1, if necessary.
Switch off monitoring (C0591 = 3).
x063 CE2 Communication error on the process data
input object CAN2_IN
CAN2_IN object receives faulty data or
communication is interrupted.
Check wiring at X4.
Check sender.
Increase monitoring time under
C0357/2, if necessary.
Switch off monitoring (C0592 = 3).
x064 CE3 Communication error on the process data
input object CAN3_IN
CAN3_IN object receives faulty data or
communication is interrupted.
Check wiring at X4.
Check sender.
Increase monitoring time under
C0357/3, if necessary.
Switch off monitoring (C0593 = 3).
x065 CE4 BUS−OFF state of system bus (CAN) The controller has received too many faulty
telegrams via the system bus (CAN) and has
disconnected from the bus.
Check wiring at X4: Is the bus correctly
terminated?
Check shield connection of the cables.
Check PE connection.
Check bus load, reduce the baud rate if
necessary. (Observe the cable length!)
Switch off the monitoring (C0595 = 3).
x066 CE5 Time−out of system bus (CAN)
(communication error of gateway function)
For remote parameterisation (C0370,
C0371) via system bus (CAN):
Slave does not respond.
Communication monitoring time has
been exceeded.
Check wiring of system bus (CAN).
Check CAN bus configuration.
0070 U15 Undervoltage of internal 15 V voltage supply Check voltage supply.
0071 CCr System failure
Strong interference injection on the control
cables
Screen control cables
Ground or earth loops in the wiring Check wiring
Check PE connection
After troubleshooting: Deenergise the
device completely (disconnect 24 V
supply, discharge DC bus)!
0072 PR1 Checksum error in parameter set 1
CAUTION: The Lenze setting is loaded
automatically!
Fault when loading a parameter set.
Interruption while transmitting the
parameter set via keypad.
Set the required parameters and store
them under C0003 = 1.
As to PLC devices, check the use of
pointers.
The stored parameters are incompatible
with the loaded software version.
Store the parameter set under C0003 = 1
first to allow for a faults reset.
0074 PEr Program error Error in the program flow Send the parameter set (on floppy
disk/CD−ROM) with a detailed description of
the problem to Lenze.
After troubleshooting: Deenergise the
device completely (disconnect 24 V
supply, discharge DC bus)!
0075 PR0 Error in parameter set.
The operating system software has been
updated.
Storage of the Lenze setting C0003 = 1.
After troubleshooting: Deenergise the
device completely (disconnect 24 V
supply, discharge DC bus)!
x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP