9300 Servo PLC
System blocks
2.12 MCTRL_MotorControl (node number 131)
2−59
L
9300 Servo PLC EN 5.1
2.12.6 Maximum speed
The maximum speed (n
max
) is set under C0011. This value is used as a reference for the absolute and
relative setpoints selected for the acceleration and deceleration times and for the upper and lower
speed limits.
n
max
= 100 % (INT) 16384
Code LCD
Possible settings
Info
Lenze Selection
C0011 Nmax 3000 Maximum speed
Reference value for the absolute and
relative setpoint selection for the
acceleration and deceleration times.
For parameterisation via interface:
Large changes in one step should
only be made when the controller
is inhibited.
500 {1 rpm} 16000
Tip!
MCTRL_nNmaxC11 displays the maximum speed set under C0011.
Use this system variable for programming your own speed scalings.
Example: C0011 = 3000 rpm MCTRL_nNmaxC11 = 3000