2.12 MCTRL_MotorControl (node number 131)
9300 Servo PLC
System blocks
2−58
L
9300 Servo PLC EN 5.1
2.12.5 Torque limitation
Via MCTRL_nLoMLim_a and MCTRL_nHiMLim_a you can set an external torque limitation. This
means that different torques can be selected for the quadrants "driving" and "braking".
MCTRL_nHiMLim_a is the upper torque limit in [%] of the max. possible torque.
MCTRL_nLoMLim_a is the lower torque limit in [%] of the max. possible torque.
The max. possible torque is set under C0057. (^ 2−57)
Stop!
Only set positive values in MCTRL_nHiMLim_a and negative values in MCTRL_nLoMLim_a,
otherwise the speed controller may be unable to perform its intended control function. This can result
in an uncontrolled acceleration of the drive.
Tip!
If MCTRL_nHiMLim_a is not assigned (free), the upper torque limit automatically is 100 % of
the max. possible torque.
If MCTRL_nLoMLim_a is not assigned (free), the lower torque limit automatically is −100 % of
the max. possible torque.
At quick stop (QSP) the torque limitation is deactivated, i.e. the drive is operated with 100 %.