2.12 MCTRL_MotorControl (node number 131)
9300 Servo PLC
System blocks
2−66
L
9300 Servo PLC EN 5.0
2.12.17.1 OC1 − short−circuit monitoring
This monitoring function protects the drive controller.
Error
Monitoring function System variable
Possible responses
No. Display TRIP Message Warning FAIL−QSP Off
x011 OC1 Short circuit MCTRL_bShortCircuit_b
Lenze setting
Setting possible
Monitoring is actuated in the event of a short circuit in the motor phases. This can also be caused
by an interturn fault in the machine.
Monitoring can also respond during power−up if an earth fault occurs.
If monitoring responds, the drive controller has to be disconnected from the mains and the
short circuit has to be eliminated.
2.12.17.2 OC2 − earth−fault monitoring
This monitoring function protects the drive controller.
Error
Monitoring function System variable
Possible responses
No. Display TRIP Message Warning FAIL−QSP Off
x012 OC2 Earth fault MCTRL_bEarthFault_b
Lenze setting
Setting possible
The 9300 Servo PLC is equipped with earth−fault detection as standard.
If monitoring is actuated, the drive controller has to be disconnected from the mains and the
earth fault has to be eliminated.
Possible causes of an earth fault:
Short circuit to frame of the machine
Short circuit of a phase to the shield
Short circuit of a phase to PE