9300 Servo PLC
System blocks
2.12 MCTRL_MotorControl (node number 131)
2−75
L
9300 Servo PLC EN 5.0
2.12.17.10 OH4 − heatsink temperature monitoring (adjustable)
This monitoring function protects the drive controller.
Error
Monitoring function System variable
Possible responses
No. Display TRIP Message Warning FAIL−QSP Off
x054 OH4 Heatsink temperature (adjustable) MCTRL_bKuehlGreaterC0122_b
Lenze setting
Setting possible
This monitoring function is designed as an early warning stage before final disconnection of the drive
controller by means of TRIP (OH) via the monitoring function "heatsink temperature (fixed)".
(^ 2−73)
With this function the process can be influenced to avoid a switch−off of the controller at an
unfavourable moment.
Furthermore, for instance, additional fans, which would cause an unacceptable noise in
continuous operation, can also be switched on and off.
MCTRL_bKuehlGreaterC0122_b is derived from a comparator with hysteresis.
The operating threshold is set under C0122.
Hysteresis is 5 K (fixed), i. e. monitoring is reset at 5 K below the operation threshold that has
been set.
The response is set under C0582.
Code LCD
Possible settings
IMPORTANT
Lenze Selection
C0122 OH4 limit
85 Temperature threshold for heatsink
temperature prewarning
"Tht > C0122" (fault OH4)
45 {1 °C} 85
C0582 MONIT OH4
2 Configuration of monitoring
2 Warning
3 Off