Electrical installation
Wiring of system bus (CAN)
6
EDKMF2178IB DE/EN/FR 6.0
59
l
h2_can−Bus−Leitungslaenge_2178
Specification of the transmission cable
We recommend the use of CAN cables in accordance with ISO 11898−2:
CAN cable in accordance with ISO 11898−2
Cable type Paired with shielding
Impedance
120 (95 ... 140 )
Cable resistance/cross−section
Cable length 300 m 70 m/m / 0.25 0.34 mm
2
(AWG22)
Cable length 301 1000 m
40 m/m / 0.5 mm
2
(AWG20)
Signal propagation delay
5 ns/m