6 Electrical installation
Wiring of system bus (CAN)
EDKMF2178IB DE/EN/FR 6.0
62
l
h2_can−Bus−Leitungslaenge_2178
Checking the use of repeaters
Compare the values derived from Tab. 1 Total cable length (^ 60) and Tab. 2 Segment
cable length (^ 61).
ƒ If the sum of the segment cable lengths is smaller than the total cable length to be
implemented, either repeaters must be used or the cable cross−section must be
increased.
ƒ If the use of repeaters reduces the max. possible total cable length so much that it is
smaller than the total cable length to be implemented, then the cable cross−section
must be increased or less repeaters must be used or the baud rate must be
decreased.
ƒ The use of a further repeater is recommended as ...
service interface
Advantage: Trouble−free connection during bus operation is possible.
calibration interface
Advantage: The calibration/programming unit remains electrically isolated.
Example
Given
Total cable length to be implemented 450 m
Number of nodes 32
Cable cross−section 0.50 mm
2
(AWG 20)
Baud rate 125 kbps
Repeater used Lenze repeater EMF2176IB
Reduction of the max. total cable
length per repeater (EMF2176IB)
30 m
Results
Max. total cable length 630 m
(see Tab. 1 Total cable length (^ 60))
Max. segment cable length 360 m
(see Tab. 2 Segment cable length (^ 61))
Comparison The max. segment cable length is smaller than the total
cable length to be implemented.
Conclusion A repeater must be installed at the determined max.
segment cable length of 360 m.