Lenze EMF2178IB Uživatelský manuál Strana 66

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 118
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 65
7 Commissioning
Possible settings via DIP switch
EDKMF2178IB DE/EN/FR 6.0
66
l
H1inbet−HINW_Einst_aktivieren_KommModule
7 Commissioning
Possible settings via DIP switch
The front panel DIP switches serve to set:
ƒ The node address (switches 1 ... 7)
ƒ The baud rate (switches 8 ... 10)
The Lenze setting of all DIP switches is OFF.
) Note!
Settings via codes
ƒ In the Lenze setting ˘ Address switches 1 ... 7 = OFF ˘, the values are
accepted from the codes C1850/C2350 (node address) and C1851/C2351
(baud rate).
Node addresses > 99 can only be set via DIP switch.
The baud rates 10 kbps and 20 kbps can only be selected via DIP switch.
ƒ Writing the codes (e.g. with GDC via CAN) has a direct effect on the
standard device codes C0009 and C0126.
ƒ Acceptance of code changes by:
Switching off and then on again the voltage supply,
"Reset node" with C0358 = 1;
Network management command "Reset Communication";
Set C2120 (AIF control byte) = 1.
ƒ The codes are inactive if at least one address switch (1 ... 7) has been set to
ON position before a renewed mains connection.
Zobrazit stránku 65
1 2 ... 61 62 63 64 65 66 67 68 69 70 71 ... 117 118

Komentáře k této Příručce

Žádné komentáře