9400 HighLine | Parameter setting & configuration
I/O terminals
Analog outputs
120 Firmware 1.37 - 09/2006 L
7.3 Analog outputs
The controller has 2 analog outputs that can be used to output internal analog signals as
voltage signals, e.g. for analog indicator control or as setpoint for slave drives.
7.3.1 Terminal assignment/electrical data
Note!
Initialisation behaviour:
After mains switching up to the start of the application the analog outputs
remain set to 0 V.
Exception handling:
In case of a critical exception in the application (e.g. reset) the analog outputs
are set to 0 V.
Terminal Use Electrical data
X3/AO1 Voltage output 1 Level: -10 V ... +10 V
(max. 2 mA)
Resolution: 11 bits + sign
Normalisation: ±2
30
±10 V
Conversion rate: 1 kHz
X3/AO2 Voltage output 2 Level: -10 V ... +10 V
(max. 2 mA)
Resolution: 11 bits + sign
Normalisation: ±2
30
±10 V
Conversion rate: 1 kHz
X3/GA Reference potential (analog ground)