L Firmware 1.37 - 09/2006 491
9400 HighLine | Parameter setting & configuration
Diagnostics & error analysis
Error messages of the operating system
CAN on board SDO server: Faulty configuration [0x00880000]
CAN on board SDO client: Faulty configuration [0x00890000]
ProjectSelection.dat file faulty [0x008c0000]
ProjectList.dat file faulty [0x008c0001]
DeviceCFG.dat file faulty [0x008c0002]
ProjectSelection.dat missing [0x008c0003]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause Remedy
CAN on board: A configuration error has occurred in the
CAN SDO server.
Faulty project download.
Invalid SDO server settings according to DS301V402
in the Engineer or PLC Designer.
Repeat download.
Correct CAN settings in the project and regenerate
project.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause Remedy
CAN on board: A configuration error has occurred in the
CAN SDO client.
Faulty project download.
Invalid SDO client settings according to DS301V402 in
the Engineer or PLC Designer.
Repeat download
Correct CAN settings in the project and regenerate
project.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error Reformat memory module (C00002="1030") and repeat
project download.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error Reformat memory module (C00002="1030") and repeat
project download.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error Reformat memory module (C00002="1030") and repeat
project download.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error Reformat memory module (C00002="1030") and repeat
project download.