9400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00346
572 Firmware 1.37 - 09/2006 L
C00346
C00347
C00348
C00349
Parameter | Name:
C00346 | CAN heartbeat activity
Data type: BITFIELD_32
Index: 24229
d
= 5EA5
h
Value is bit-coded:
Bit 0 Heartbeat node 1
... ...
Bit 31 Heartbeat node 32
; Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00347 | CAN heartbeat status
Data type: UNSIGNED_8
Index: 24228
d
= 5EA4
h
Selection list (display only)
0Unknown
4 Stopped
5Operational
127 Pre-operational
Subcodes Information
C00347/1 Status node 1 ... 32
C00347/...
C00347/32
; Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00348 | CAN status DIP switch
Data type: UNSIGNED_8
Index: 24227
d
= 5EA3
h
The value "1" means that the CAN DIP switch has been identified after mains switching and a valid baud rate and
node address have been set.
"0" means that no CAN DIP switch or no valid setting has been identified or the setting has been overwritten by
writing code C00350
or C00351.
Display range
(min. value | unit | max. value)
01
; Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00349 | DIP switch CAN setting
Data type: UNSIGNED_8
Index: 24226
d
= 5EA2
h
Setting of the CAN DIP switch at the last mains connection
Display range
(min. value | unit | max. value)
0 255
Subcodes Information
C00349/1 Node address
C00349/2 Baud rate:
0: 10 kbit/s
1: 20 kbit/s
2: 50 kbit/s
3: 125 kbit/s
4: 250 kbit/s
5: 500 kbit/s
6: 800 kbit/s
7: 1000 kbit/s
; Read access Write access CINH PLC STOP No transfer COM MOT