9400 HighLine | Parameter setting & configuration
Diagnostics & error analysis
Error messages of the operating system
452 Firmware 1.37 - 09/2006 L
Safety module is defective or missing [0x0068000d]
Control card is not compatible [0x0068000e]
Power section is not compatible [0x0068000f]
MXI1: Wrong module [0x00680010]
MXI2: Wrong module [0x00680011]
Wrong memory module [0x00680012]
Response (Lenze setting printed in bold)
None : System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Operating system could not identify the safety module. Use a different safety module.
Please contact Lenze.
Response (Lenze setting printed in bold)
None : System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The control card is not supported by the operating
system.
Please contact Lenze.
Response (Lenze setting printed in bold)
None : System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The power section is not supported by the operating
system.
Please contact Lenze.
Response (Lenze setting printed in bold)
None : System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The extension module in the module receptacle MXI1 is
not supported by the operating system.
Use a different module.
Please contact Lenze.
Response (Lenze setting printed in bold)
None : System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The extension module in the module receptacle MXI2 is
not supported by the operating system.
Use a different module.
Please contact Lenze.
Response (Lenze setting printed in bold)
None : System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The memory module is not supported by the operating
system.
Use a different module.
Please contact Lenze.