9400 HighLine | Parameter setting & configuration
Diagnostics & error analysis
Error messages of the operating system
462 Firmware 1.37 - 09/2006 L
Read error - service register [0x00720000]
External error [0x00750000]
Controller is enabled [0x00750001]
Controller has been initialised [0x00750002]
Controller in STO state [0x00750003]
Controller: Pulse inhibit is active [0x00750005]
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
An error has occurred while reading or writing the service
register.
Mains switching
Please contact Lenze, if the problem occurs again.
Response (Lenze setting printed in bold) Setting: C00581 (; Adjustable response)
; None System fault : Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
The drive interface has activated the error message
"External error".
•The input DI_bSetExternError of the system block
LS_DriveInterface has been set to TRUE.
Check external device to be monitored.
Check assignment of the input DI_bSetExternError in
the application.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause Remedy
The controller is enabled and has the "Operation" state. - (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause Remedy
The controller has left the "Initialisation active" state. - (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause Remedy
The controller has received the "safe torque off" request
and is now in the "Safe Torque Off active" state.
- (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause Remedy
The pulse inhibit is active in the controller. - (Information only)