4 Drive interface
4.3 Device states
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.3.9 "Trouble active" state
This device state becomes active as soon as a monitoring function responds for which the "Trouble"
error response has been parameterised.
The motor has no torque (is coasting).
The device state is automatically exited if the error cause is eliminated:
"Trouble active" state < 500 ms: Return to the original device state.
"Trouble active" state > 500 ms: Return via the device state "Safe torque off active".
4.3.10 "Fault active" state
This device state becomes active as soon as a monitoring function responds for which the "Fault"
error response has been parameterised.
4.3.11 "System fault active" state
This device status becomes active if a system fault occurs.
The device state can only be exited by mains switching.
LED DRIVE READY LED DRIVE ERROR Display in C00183
OFF 104: Trouble active
LED DRIVE READY LED DRIVE ERROR Display in C00183
OFF 102: Fault active
LED DRIVE READY LED DRIVE ERROR Display in C00183
OFF 20: System fault active