Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 223
5 Motor interface
5.9 Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.9.3.1 Specific characteristic for the motor temperature sensor
A specific characteristic can be defined and activated for the motor temperature sensor if required.
The specific characteristic is defined on the basis of two grid points which must be set in C01191
and C01192
. Those two points define a line which is extrapolated to the right and to the left.
The special characteristic is activated by setting C01190
="1".
In the Lenze setting, the specific characteristic is defined as follows:
[5-37] Lenze setting of the specific characteristic
The following applies from software version V4.0:
Sometimes a short circuit is a desired state (e.g. temperature contact closed below 140 °C). For
this purpose, the interpolation point 1 (C01191/1
) must be below 122 Ω to prevent the
triggering of sensor errors. In this case the temperature continues to be calculated.
Interpolation point
C01191/1
= 25 °C
C01192/1
= 1000 Ω
Interpolation point
C01191/2
= 150 °C
C01192/2
= 2225 Ω
0
1000
2225
0 150
W
°C
25
Note!
If a motor is selected from the motor catalogue, parameters C01190, C01191, and
C01192
are overwritten!
If the controller measures a resistance below 122 Ω, this is interpreted as a sensor
error and a temperature of 255 °C is output.