Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 105
4 Drive interface
4.4 Automatic restart after mains connection/trouble...
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Auto-start option 1: Auto restart enabled after mains connection
The following illustration shows the state changes for the auto-start option 1 and their relationship
to controller inhibit:
[4-26] State change when auto-restart is enabled (C00142 = "1: Enabled")
Controller pulses are inhibited
Controller pulses are enabled
With controller inhibit after power-on
Without controller inhibit after power-on
RFR
01
RFR
RFR
RFR
t
t
Initialisation Switched on OperationReady to switch on
OperationInitialisation Switched onReady to switch on