5.9.5 Maximum current monitoring
The ultimate motor current I
ULT
to be parameterised in C00620 is a limit value to protect the motor
from destruction or influence of the rated data.
• This limit value must not be travelled cyclically in the drive process.
• The maximum current parameterisable in C00022
should have a sufficient distance from this
limit value.
• If the instantaneous value of the motor current exceeds the limit value set in C00620
the
response set in C00619
is executed for motor protection (Lenze setting: Fault).
Note!
When you select a Lenze motor from the catalogue and transfer the plant parameters of
the motor to the controller, the setting in C00620
is automatically adjusted to the
selected motor.