5 Motor interface
5.6 V/f control (VFCplus)
190
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.6.2.2 Parameterising slip compensation
The slip compensation serves to automatically compensate a load-dependent speed loss. In order
that the slip compensation can operate correctly, the rated slip of the motor is required. This is
calculated from the rated frequency (C00089
) and the rated speed (C00087), thus both parameters
must be parameterised correctly.
A percentage adjustment of the calculated slip can be made in C00965
, e.g. when the real motor
data deviate from the data given on the nameplate. A value of 100 % in C00965
corresponds to
the rated slip of the machine.
The time behaviour of the slip compensation can be parameterised in C00966
.
Short overview: Parameters for slip compensation
Parameter Info Lenze setting
Value Unit
C00965 VFC: Gain - slip compensation 0.00 %
C00966 VFC: Time const. slip comp. 2000 ms