Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 867
14 Parameter reference
14.2 Parameter list | C02605
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C02605
C02607
C02608
Parameter | Name:
C02605 | Brake test - time
Data type: UNSIGNED_16
Index: 21970
d
= 55D2
h
From software version V10.0
Setting range (min. value | unit | max. value)
0.001 s 65.535
Subcodes Lenze setting Info
C02605/1 1.024 s Brake test - ramp-up time
C02605/2 4.000 s Brake test - constant ph. time
C02605/3 1.024 s Brake test - ramp-down time
Read access Write access CINH PLC STOP No transfer Scaling factor: 1000
Parameter | Name:
C02607 | BRK_dnState
Data type: INTEGER_32
Index: 21968
d
= 55D0
h
Bit coded status of the basic function "Brake control".
Display range (min. value | unit | max. value)
-2147483648 2147483647
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C02608 | BRK_dnTorqueAdd_n
Data type: INTEGER_32
Index: 21967
d
= 55CF
h
Display of the additive torque value of the basic function "brake control".
Display range (min. value | unit | max. value)
-200.00 % 200.00
Read access Write access CINH PLC STOP No transfer Scaling factor: 100