14 Parameter reference
14.2 Parameter list | C00360
774
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00360
C00361
Parameter | Name:
C00360 | CAN telegram and error counter
Data type: UNSIGNED_16
Index: 24215
d
= 5E97
h
• After mains connection all counters start with "0".
• After the maximum value has been reached, counting restarts with "0".
"CAN on board" system bus
Display range (min. value | unit | max. value)
0 65535
Subcodes Info
C00360/1 Stuffing bit error counter
• More than five identical bits have been detected.
C00360/2 Format error counter
• CAN frame has not been observed.
C00360/3 Acknowledge error counter
• No device has acknowledged the telegram.
C00360/4 Bit1 error counter
•"1" should be sent after bus arbitration, but "0" was
read.
C00360/5 Bit0 error counter
•"0" should be sent after bus arbitration, but "1" was
read.
C00360/6 CRC error counter
• Checksum check has indicated an error.
C00360/7 Tx telegram counter
• Correctly received telegrams.
C00360/8 Rx telegram counters
• Correctly transmitted telegrams.
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00361 | CAN bus load
Data type: UNSIGNED_32
Index: 24214
d
= 5E96
h
The display of the node peak load (subcodes 4 ... 6) is reset by repeated mains switching or via the "Reset node"
device command (C00002
).
"CAN on board" system bus
Display range (min. value | unit | max. value)
0 % 100
Subcodes Info
C00361/1 Current node load in Tx direction
C00361/2 Current node load in Rx direction
C00361/3 Current node load through faulty telegrams
C00361/4 Maximum node load in Tx direction
C00361/5 Maximum node load in Rx direction
C00361/6 Maximum node load through faulty telegrams
Read access Write access CINH PLC STOP No transfer Scaling factor: 1