Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 891
14 Parameter reference
14.2 Parameter list | C02765
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C02765
C02770
C02771
Parameter | Name:
C02765 | Enc_bError
Data type: UNSIGNED_32
Index: 21810
d
= 5532
h
From software version V7.0
Encoder evaluation: Provision of the encoder signal of input X8
Selection list (read only)
0 FALSE
1 TRUE
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C02770 | Operating mode
Data type: UNSIGNED_32
Index: 21805
d
= 552D
h
From software version V7.0
Basic function "Manual jog open loop
"
Selection list (Lenze setting printed in bold)
0Deactivate
1Activate
Subcodes Lenze setting Info
C02770/1 0: Deactivate EnableManualMode
C02770/2 0: Deactivate JogPositive
C02770/3 0: Deactivate JogNegative
C02770/4 0: Deactivate SelectTab1
C02770/5 0: Deactivate SelectTab2
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C02771 | Frequency
Data type: INTEGER_32
Index: 21804
d
= 552C
h
From software version V7.0
Basic function "Manual jog open loop
"
Setting range (min. value | unit | max. value)
0.0 Hz 1000.0
Subcodes Lenze setting Info
C02771/1 1.0 Hz Frequency 1
C02771/2 1.0 Hz Frequency 2
C02771/3 1.0 Hz Frequency 3
C02771/4 1.0 Hz Frequency 4
Read access Write access CINH PLC STOP No transfer Scaling factor: 10