Parameter | Name:
C00064 | Device utilisation (Ixt)
Data type: UNSIGNED_32
Index: 24511
d
= 5FBF
h
Device utilisation during the last 180 seconds
• C00064 > 100 % activates error (OC5).
• Error reset only possible if C00064 < 95 %.
Display range (min. value | unit | max. value)
0 % 250
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00065 | Ext. 24-V voltage
Data type: INTEGER_32
Index: 24510
d
= 5FBE
h
Display range (min. value | unit | max. value)
0.0 V 1000.0
Read access Write access CINH PLC STOP No transfer Scaling factor: 10
Parameter | Name:
C00066 | Thermal motor load (I²xt)
Data type: UNSIGNED_32
Index: 24509
d
= 5FBD
h
A 100 % load corresponds to a permanently flowing rated motor current
I2xt motor monitoring
Display range (min. value | unit | max. value)
0 % 250
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00068 | Capacitor temperature
Data type: INTEGER_32
Index: 24507
d
= 5FBB
h
Display range (min. value | unit | max. value)
-200 °C 200
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00069 | CPU temperature
Data type: INTEGER_32
Index: 24506
d
= 5FBA
h
Display range (min. value | unit | max. value)
-200 °C 200
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00070 | Speed controller gain
Data type: UNSIGNED_32
Index: 24505
d
= 5FB9
h
Setting range (min. value | unit | max. value) Lenze setting
0.00000 Nm/rpm 20000.00000 0.00044 Nm/rpm
Read access Write access CINH PLC STOP No transfer Scaling factor: 100000