Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 739
14 Parameter reference
14.2 Parameter list | C00071
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00071
C00072
C00074
C00075
C00076
C00077
Parameter | Name:
C00071 | Speed contr. reset time
Data type: UNSIGNED_32
Index: 24504
d
= 5FB8
h
Setting range (min. value | unit | max. value) Lenze setting
1.0 ms 6000.0 14.4 ms
Read access Write access CINH PLC STOP No transfer Scaling factor: 10
Parameter | Name:
C00072 | Speed contr.D component
Data type: UNSIGNED_32
Index: 24503
d
= 5FB7
h
Setting range (min. value | unit | max. value) Lenze setting
0.00 ms 3.00 0.00 ms
Read access Write access CINH PLC STOP No transfer Scaling factor: 100
Parameter | Name:
C00074 | Feedfwd. ctrl. - current contr.
Data type: UNSIGNED_8
Index: 24501
d
= 5FB5
h
Selection list (Lenze setting printed in bold)
0 Deactivate feedfwd. ctrl
1 Activate feedfwd. ctrl
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00075 | Current controller gain
Data type: UNSIGNED_32
Index: 24500
d
= 5FB4
h
Setting range (min. value | unit | max. value) Lenze setting
0.00 V/A 750.00 105.00 V/A
Read access Write access CINH PLC STOP No transfer Scaling factor: 100
Parameter | Name:
C00076 | Current contr. reset time
Data type: UNSIGNED_32
Index: 24499
d
= 5FB3
h
Setting range (min. value | unit | max. value) Lenze setting
0.01 ms 2000.00 2.00 ms
Read access Write access CINH PLC STOP No transfer Scaling factor: 100
Parameter | Name:
C00077 | Field controller gain
Data type: UNSIGNED_32
Index: 24498
d
= 5FB2
h
Setting range (min. value | unit | max. value) Lenze setting
0.00 A/Vs 50000.00 165.84 A/Vs
Read access Write access CINH PLC STOP No transfer Scaling factor: 100