Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 829
14 Parameter reference
14.2 Parameter list | C00980
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00980
C00985
C00986
C00987
C00988
Parameter | Name:
C00980 | VFC: Override point of field weakening
Data type: INTEGER_32
Index: 23595
d
= 5C2B
h
From software version V8.0
Offset of the override point of field weakening
In the VFCplus operating mode the pull-out protection function or the maximally permissible current in the field
weakening range can be adapted.
Setting range (min. value | unit | max. value) Lenze setting
-500 Hz 500 0Hz
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00985 | SLVC: Field current controller gain
Data type: UNSIGNED_32
Index: 23590
d
= 5C26
h
From software version V3.0
Sensorless vector control
Setting range (min. value | unit | max. value) Lenze setting
0.00 21474836.47 0.00
Read access Write access CINH PLC STOP No transfer Scaling factor: 100
Parameter | Name:
C00986 | SLVC: Cross current controller gain
Data type: UNSIGNED_32
Index: 23589
d
= 5C25
h
From software version V3.0
Sensorless vector control
Setting range (min. value | unit | max. value) Lenze setting
0.00 21474836.47 0.00
Read access Write access CINH PLC STOP No transfer Scaling factor: 100
Parameter | Name:
C00987 | SLVC: Gain - torque controller
Data type: UNSIGNED_32
Index: 23588
d
= 5C24
h
From software version V3.0
Sensorless vector control
Setting range (min. value | unit | max. value) Lenze setting
0.0000 Hz/A 1000.0000 0.5000 Hz/A
Read access Write access CINH PLC STOP No transfer Scaling factor: 10000
Parameter | Name:
C00988 | SLVC: Reset time - torque contr.
Data type: UNSIGNED_32
Index: 23587
d
= 5C23
h
From software version V3.0
Sensorless vector control
Setting range (min. value | unit | max. value) Lenze setting
0.01 ms 2000.00 10.00 ms
Read access Write access CINH PLC STOP No transfer Scaling factor: 100