Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 703
13 Diagnostics & fault analysis
13.7 Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Cam data locked due to incorrect password [0x00b80016]
Cam data locked due to incorrect safety key [0x00b80017]
Homing mode not allowed [0x00b80019]
Int. overflow C02620 (manual jog: Speed 1) [0x00b8001a]
Module ID (decimal) Error ID (decimal)
184: Basic drive functions 22
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The cam data were locked since the user password was
entered incorrectly for three times.
The cam data were not loaded.
Reset parameters to the Lenze setting via device
command C00002
= "0: Load Lenze setting". Then
download cam data again.
Module ID (decimal) Error ID (decimal)
184: Basic drive functions 23
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The cam data were not loaded because the safety key is
damaged.
The password in the cam data or the serial number of the
memory module has been manipulated.
Reset parameters to the Lenze setting via device
command C00002
= "0: Load Lenze setting". Then
download cam data again.
Module ID (decimal) Error ID (decimal)
184: Basic drive functions 25
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
From software version V3.0
The homing mode selected in C02640
is not supported in
the motor control type selected in C00006
.
Select another homing mode in C02640
.
Module ID (decimal) Error ID (decimal)
184: Basic drive functions 26
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
From software version V3.0
Due to a subsequent change of the machine parameters
for gearbox ratio, feed constant, or resolution of an
encoder revolution, the value set in the parameter
cannot be displayed in the internal unit. See chapter
"Max. position, speed, and acceleration that can be
displayed internally".
• Check machine parameters and adapt them if
required.
• Change setting in C02620
.